1.4. QUINT UPS Battery Change

The UPS battery modules can be easily changed when needed using the following procedure:

 

1. Place the QUINT UPS into service mode by pressing and holding the service mode button located on the from of the UPS module. Press and hold this button for 6 seconds to put the UPS into service mode.

2. Open the battery casing using the spring clips at the top.

3. Remove the battery fuse.

4. Disconnect the battery cell wiring from the cells.

5. Remove the old cells and install the replacement cells.

6. Reconnect the battery cell wires.

7. Re-install the battery fuse.

8. Return the UPS module to normal mode by pressing and holding the service mode button for six seconds.

A video of the full procedure can be found on the Phoenix Contact Website. Navigate to the downloads section of the battery modules information page. Once there, click on "E-Learning" and download the battery change tutorial video shown below.

https://www.phoenixcontact.com/en-pc/products/energy-storage-ups-bat-pb-24dc-4ah-1274117